FabFive --- 12 years ago -

Our a/c is not kicking on outside. Sometimes when I walk by a vent and feel it's blowing, but barely, almost imperceptible. This happened sometime this afternoon and I didn't realize until it warmed up in here. We had very heavy storms earlier today and not sure if that had an impact? The thermostat is reading properly, showing where it's set and what the actual temp is. If I turn the unit off entirely with the thermostat and turn it back on nothing happens.

DH is pretty handy and can check some stuff out when he gets home, but can someone please tell me what to have him check this evening based on what the most likely causes are? Obviously can't call a repairman until the morning. 

Gigix4 --- 12 years ago -

Fan motor? (on the outside unit)

At least that's what it was when the same thing happened at my mother's house.

If I remember right, it cost me $400 to have it fixed by a pro so if hubby can do it (if he can get his hands on a motor) I'm sure it would be less. 

Emperor of Kingwood --- 12 years ago -

Sounds like the evaporator is blocked, perhapes by ice. This happens due to low freon. 

FabFive --- 12 years ago -

Gigi good point on the fan motor. Do you know how he would determine if that were the cause?

Bob wouldn't I see ice? And I thought with low Freon it sort of quit blowing cold for awhile before hand? It's been blowing cold. 

Gigix4 --- 12 years ago -

Do you know how he would determine if that were the cause?

The way I knew it was the fan was that the unit (inside) would come on but nothing was happening at the compressor (outside) unit. But I'm certainly no expert. The same thing may happen if the compressor is gone! 

Emperor of Kingwood --- 12 years ago -

You wont see ice unless you go to the air handler and look at the evaporator.

It depends on how low it is. Too low and the compressor wont kick on. Slightly low and it will freeze up. 

FabFive --- 12 years ago -

We had this same thing happen a year ago and it was the capacitor. It was less than $100 and I really appreciated that. Now I'm wondering if it's that again? We could only be so lucky. But it seems like it could also be the compressor, the fan motor, or maybe even a flipped breaker? There's a box outside on the side of the house and I'm not sure what it's for and I'm too chicken to go flipping breakers until DH gets home. I was wondering if maybe the storm had something to do with a breaker or the capacitor? 

FabFive --- 12 years ago -

Bob where's the air handler? Sorry I am an a/c dolt. Maybe I should you tube it. 

Emperor of Kingwood --- 12 years ago -

Its possible but a remote possibility. There are two major components to the outdoor unit; the compressor and the fan motor. Both have to be functioning. However, the fan motor can be running but not the compressor, but not the other way around.

Check the breaker in your main breaker box. It should be a double breaker. Reset if necessary.

On the inside, set the thermostat from auto to fan and make sure the air handler is working by blowing air out the vents. If not, and the inside fan is running, the ice is likely blocking the evaporator. 

Emperor of Kingwood --- 12 years ago -

The air handler is usually in the attick. 

MonzaRacer --- 12 years ago -

Check the breaker in your main breaker box. It should be a double breaker. Reset if necessary.


Check this first FF...if it is tripped it will be easy to spot as the little handle on the breaker will be out of alignment with the others... 

MonzaRacer --- 12 years ago -

Oops, double post 

FabFive --- 12 years ago -

OK. Checked breaker on main box and it's fine.

Then went to thermostat (I have had the unit off for about 30-45 minutes) and clicked fan to ON. It kicked on outside and air was blowing through vents. Then clicked fan to "auto" and system to cool. It's still on. 

FabFive --- 12 years ago -

No sooner did I post then the damn thing turned off. 

FabFive --- 12 years ago -

OK the outside unit is still running but the part I hear in the attic isn't running any more. This can't be good. 

Emperor of Kingwood --- 12 years ago -

Leave the system oc cool, and position the auto/fan switch to fan.

The air handler in the attick should kick on as well as the outside fan and compressor.

If you go into the attick with it on and listen and put your hand on the airhandler, you should feel the vibration of it running, if it is. 

FabFive --- 12 years ago -

I turned the whole thing off again at the thermostat. 

Emperor of Kingwood --- 12 years ago -

Most thermostats have a +- 3 to 4 degree differential before the unit will kick on. 

FabFive --- 12 years ago -

Mine comes on within 1 degree. It's the digital kind. Also, it's reading 81 and I've got it set at 76. 

FabFive --- 12 years ago -

Well when I switched the fan on and then switched it to cool, I could hear it kick on in the attic too. I reached up to the vent and it was blowing cold. Then like a minute later the attic noise kicked off and the outside one stayed on. 

Emperor of Kingwood --- 12 years ago -

Ahhh ok, then theres an issue with the air handler fan motor. Sounds like it might be overheat trip on the fan motor. 

FabFive --- 12 years ago -

So how do I fix this? What do I tell DH to look at? Is this a job for a professional or is this a part he can buy at Home Depot? 

FabFive --- 12 years ago -

Here are some things he's going to check:

capacitor

fan blower in the attic

is there a fan filter in the attic? If so, he will check that

where would the frozen coil be? Attic or outside? Nothing is frozen outside

Would the outside fan still work if the circuit board is bad? 

Emperor of Kingwood --- 12 years ago -

No, you are going to have to call a company for that one. Just double check everything and verify that the air handler fan is shutting off after a couple minutes of running. If thats happening, it sounds like the fan motor is cutting off on thermal overload. It has a protective circuit for that.

Thermal overload can be caused by overheating of the motor windings due to the breakdown of the motor winding insulation causing a reduction in insulation resistance which causes temperature to rise.

Also, thetmal overload can be caused by dirty air filters, but not likely in your case. 

Emperor of Kingwood --- 12 years ago -

If the outside fan is coming on, the capacitor is good. Same goes for the air handler motor in the attick.

Its not likely a frozen coil since the air handler motor is shutting off. 

FabFive --- 12 years ago -

Well the filter was dirty and I changed it, but it wasn't like crazy dirty. Wouldn't it be working then once I changed it if it was due to the filter?

OK thanks for info on capacitor and blower. So we just need a new blower probably? 

Emperor of Kingwood --- 12 years ago -

Likely a new blower motor. 

FabFive --- 12 years ago -

OK thank you 